Abstract

The hot air recirculation phenomenon observed in direct air- cooled system is numerical simulated and the causes of the hot air recirculation and its influence on air-cooled units are qualitatively analyzed with the help of computational fluid dynamics (CFD) software. The results indicate that the hot air recirculation is a common trouble in the air-cooled power units. It is provoked by the arrangement of the air-cooled island and the environmental condition around the direct air-cooled system, especially the strong wind. The hot air recirculation greatly reduces the heat transfer ability, which will worsen units' vacuum and cause the power units to trip out.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call