Abstract

The performances of ventilation in the buildings with quadrate and cylindrical cross-sections are compared numerically. The incoming jet in the cylindrical unsheltered-building is more horizontal in comparison to the quadrate unsheltered-building. The dimensionless volume flow rates in the quadrate and cylindrical unsheltered-buildings are respectively 0.503 and 0.553. The incoming jet in the sheltered-buildings flows to the floors immediately. The velocity near the floor in the cylindrical sheltered-building is greater than that in the quadrate sheltered-building. The dimensionless volume flow rates in the quadrate and cylindrical sheltered-buildings are respectively 0.130 and 0.210.Comparing with the quadrate buildings, the ventilation rates in the cylindrical unsheltered and sheltered buildings increased by 10% and 61%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.