Abstract
In conventional vapor compression and absorption refrigeration systems, a compressor or a mechanical pump, respectively circulates the refrigerant. Mechanical input, which is required by the compressor or the pump operation, contributes significantly to the noise level and lessens its reliability and portability. In contrast, diffusion absorption refrigeration (DAR) systems are heat-driven and contain no moving parts. Solar-driven diffusion absorption cooling system uses a low-grade heat to produce a cooling effect, and it's specially tuned for remote locations with high levels of solar radiation. This article studies the performance of a DAR system in Ashdod, Israel. Based on existing models in the literature and on experimental measurement of quantities such as the solar irradiance and the air temperature, the cooling capacity and the COP were simulated. Cooling capacity of the DAR system varies between 100 and 140 W, and COP between 0.09 and 0.17.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.