Abstract

This paper presents an analysis method based on explicit dynamic analysis, enabling detailed and representative investigations of the mechanical effects of low-impedance faults in power equipment. To illustrate the effectiveness of the proposed method, a given transformer design having caused the projection of a heavy chimney/bushing assembly over a significant distance is used as a case study. A comparison about the observed projection distance of this assembly shows that the method provides representative results, thus offering the significant advantage of replacing costly and unpractical tests. The method is then used to study the retrofit measure proposed in this case to retain the chimney, further exemplifying its power to effectively study different design and retrofitting options.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.