Abstract
The current 3-D numerical analysis explores the effect of combinations of rectangular winglet pairs (RWPs) having different attack angles (i.e. 5°, 15° and 25°) along a row of the tube array, on the performance of the fin and tube heat exchanger (FTHE). The considered airside Reynolds number Re ranges from 500 to 900. In total, six combinations of three attack angle vortex generators (VGs) have been numerically analysed namely 5°-15°-25°, 5°-25°-15°, 15°-5°-25°, 15°-25°-5°, 25°-5°-15° and 25°-15°-5°. The performance of the FTHE is represented by area goodness factor. The performance rankings of the FTHEs are also obtained by the MOORA method. Finally, 5°-25°-15° case provides the best thermal hydraulic performance for which heat transfer coefficient (h) is increased by 68.20% at Re = 500 and 81.78% at Re = 900, with a significant pressure drop penalty.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.