Abstract

In the present work, a numerical investigation has been performed to find out the best emplacement of rectangular winglet pairs (RWPs) for the improvement of the heat transfer and flow characteristics of a fin and tube compact heat exchanger at low Reynolds number ranges from 500 to 900. The RWPs are placed at two different locations i.e., adjacent to the tubes and behind the tubes namely, common-flow-up (CFU) and common-flow-down (CFD) orientations respectively. The effect of attack angle, span angle and location of RWPs on air-side thermal hydraulic performance is investigated numerically. Area goodness factor and heat transfer rate per unit fan power are considered as the performance evaluation criteria. It is found that with the increase in attack angle and span angle heat transfer rate increases causing an increase in pressure drop penalty as well. Vortex generators behind the tube can reduce the pressure drop but with a significant reduction in heat transfer. Furthermore, MOORA (Multi-objective optimization by ratio analysis) method is employed to obtain the most expedient position and orientation of RWPs.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.