Abstract

Based on expressions for transient three-phase short-circuit current, the formulas for radial and axial electromagnetic forces acting on transformer windings are derived. The short-circuit forces, include three components: DC component, fundamental-frequency component, and double-frequency component. Using a 17000-kVA transformer as a model, the 2-D leakage magnetic fields and forces with various phase angles are calculated by the finite-element method. The results are compared with design formulas. Numerical calculations show that the conventional design formulas used to calculate radial force can meet engineering needs.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.