Abstract

The Simplified model of both calculating leakage magnetic field and mechanical force of windings at short circuit condition for a 120MVA/220kV power transformer is set up. The leakage magnetic field ‚ short-circuit force and stress in transformer windings are analyzed and their distributing characteristics are acquired respectively by using FEM. The calculation method and results are validated by withstanding short circuit strength test of the product. A number of useful suggestions are given for design of power transformers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.