Abstract

The thermal performance of a wickless heat pipe receiver for parabolic trough solar collector applications is investigated in this study. For three filling ratios of 30%, 50%, and 90%, nine different heat flux profiles were examined. The normal heat flux range was chosen to be between 58 and 288 W/m2. The influence of the non-homogeneity of the thermal flux on the receiver tube was numerically analysed for various filling ratios. The maximum average wall temperature of 390 K was observed for heat transfer profile 7 and a fill ratio of 30%. For a filling ratio of 90%, the heat flux profile 7 had a minimum thermal resistance of 0.245 K/W, and a correlation was proposed to calculate the thermal resistance. A maximum thermal resistance of 1.722 K/W was calculated for the heat flux profile 3 and a filling ratio of 30%.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.