Abstract

This article presents a new numerical algorithm suitable for defining recloser reclaim time and blocking automatic reclosing during permanent faults on overhead lines. It is based on terminal voltage input data processing. The decision if it is safe or not to reclose is determined from the voltage signal of faulted and tripped line phase using fundamental and third harmonic calculated by discrete Fourier transform. The algorithm was successfully tested using signals recorded on the real power system. The tests demonstrate the ability of presented algorithm to determine the secondary arc extinction time and to block unsuccessful automatic reclosing of HV lines with permanent fault.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.