Abstract

Heat transfer measurements were made during nucleate boiling of R-113 from a bundle of 15 electrically heated, copper TURBO-B tubes arranged in an equilateral triangular pitch, designed to simulate a portion of a flooded evaporator. Five of the tubes that were oriented in a vertical array on the centerline of the bundle were each instrumented with six wall thermocouples. For increasing heat flux, the incipient boiling wall superheat of upper tubes decreased as lower tubes were activated. In the boiling region at low heat fluxes (≈ 1 kW/m2), the average bundle heat transfer coefficient was 4.6 times that obtained for a smooth tube bundle (under identical conditions) and 1.6 times greater than that obtained for a single TURBO-B tube; a similar bundle factor has been reported for a smooth tube bundle. At high heat fluxes (100 kW/m2), the average bundle heat transfer coefficient was 3.6 times that of a smooth tube bundle. Furthermore, there was still a significant bundle factor (1.22), contrary to a smooth tube bundle, where all effect of lower tubes was eliminated at high heat fluxes.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.