Abstract

Maintenance and repair of circuit breakers (CBs) due to their protective role in the power systems is the centre of attention and assessing their condition is tremendously important. The interruption chamber of the CBs including main contacts is highly subjected to erosion over time due to friction, and excessive heat produced by an arc during the interruption of the currents. This study presents a new high-frequency (HF) non-intrusive diagnostic technique for the deterioration of contacts used in high-voltage CBs. The most striking result to emerge from the investigations is that the resonance frequency highly relies on the condition of contacts. The proposed approach is implemented in Computer Simulation Technology Studio Suite software and compared with the measured data obtained through the static resistance measurement. In addition, a HF model based on the transmission line theory has been developed for the interruption chamber of CBs. The comparison of the obtained results via a novel HF-based approach with the experimental data validates the feasibility and accuracy of this approach in analysing the ablation of contacts used in the interruption chamber of CBs.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.