Abstract

An inrush current is a transient current that results from a sudden change in the exciting voltage across a transformer's windings. It may cause inadvertent operation of the protective relay system and necessitate strengthening of the transformer's mechanical structure. A novel approach to reducing the inrush current of power transformer, by increasing the transient inductance of the primary coil by changing the distribution of the coil winding is presented. During the period of this study, 30 patterns of 220 V/110–220 V 5 kVA-power transformers with three-layer and four-layer winding structures were developed as demonstrations of the approach. According to field tests and theory, the proposed method successfully limits the inrush current.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.