Abstract

BackgroundLimited post-marketing data exist on the use of the Solitaire FR device in clinical practice. The North American Solitaire Stent Retriever Acute Stroke (NASA) registry aimed to assess the real...

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.