Abstract

Normal values for asymmetric prism bar vergences were derived from the clinic population of the School of Optometry, University of Alabama in Birmingham. The means, standard deviations, effect of order of prism presentation, and eye dominance were examined for three clinical groups. The results provide standards for prism bar vergence and demonstrate that order of testing and dominance have no significant effect upon the values obtained.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.