Noise measurements were performed in eight patients' rooms, three intensive care units (ICUs) and one operating theatre at a large hospital (1300 beds). Daytime and nighttime LAeq in patients' rooms and in ICUs were higher than the recommended standards. The measured noise levels could interfere with normal sleep and could be dangerous for patients at greatest risk. The laminar flow ventilation system was the main source of noise in the operating room. The LAeq recorded during a surgical procedure was sufficiently high to mask speech communication.The measurement of A-weighted sound pressure levels disclosed that staff activities were responsible for the loudest noises. Air-conditioning systems and electro-mechanical instruments were also important contributors to noise pollution in the hospital.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.