Abstract
This research focused on the communication noise level depending on the distance for conventional fire detection systems (RS-485 codetransmitter) in comparison to the newly developed optical cable automatic fire detection system (optical communication code-transmitter. The noise levels of the RS-485 code-transmitter were respectively 10, 200, 1200, and 2400 mV for the communication distances of 0, 1, 40, and 80 m and showed a correlation between the increase of the communication noise with the increase of the communication distance. However, the optical communication code-transmitter did not show any sign of communication noise at these four different distances. Therefore, the newly developed optical communication system is an ideal system to avoid false alarms in automatic fire detection system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.