Abstract

A new effective method for reducing harmonics involved in input ac line currents or output dc voltage of the thyristor rectifier apparatus with an interphase transformer is proposed. This method is based on the sophisticated utilization of several thyristors inserted in parallel between several taps equipped symmetrically for the midpoint of the interphase transformer and the terminal of the dc output circuit. The key point of this method can be understood easily when compared with conventional use of the interphase transformer, where the dc output circuit is taken from the midpoint of the interphase transformer directly. The features of this method are very simple and very economical in circuit construction. Their presentation will take the following form: 1) fundamental theory of the method; 2) analysis of waveforms of input ac line currents under optimum operation; 3) checking the validity of the theory by experiment using the six-phase 12-pulse thyristor polyphase rectifier apparatus; 4) various modifications of this method.