Abstract
In this work a new method to optimize the COP in water- and air-cooled single and double effect LiBr/H 2O absorption chillers is proposed. This method determines the effect of condensation temperatures and the solution concentration variation on COP, clearly defining the crystallization limit for different scenarios. This limit is especially important in the design of air-cooled chillers. Taking this into account a simulation program has been developed to calculate the optimum COP. In the case of parallel flow double effect chillers this program estimates not only the optimum COP but also the percentage of refrigerant vapour generated in the high and low temperature desorbers in terms of the condensation temperature. Additionally it provides the mass flow of the solution that should be distributed to each desorber to attain the desired variation in solution concentration.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.