Abstract

Due to the rapidly growing renewable power, the fossil fuel power plants have to be increasingly operated under large and rapid load change conditions, which can induce various challenges. This work aims to reduce NOx emissions of large-scale corner-fired boilers operated at medium–low loads. The combustion characteristics and NOx emissions from a 1000 MWe corner-fired tower boiler under different loads are investigated experimentally and numerically. A new control strategy for the annular fuel air is proposed and implemented in the boiler, in which the secondary air admitted to the furnace through the air annulus around each coal nozzle tip is controlled by the boiler load, instead of being controlled by the output of the connected mill as commonly used in this kind of power plant. Both the experimental and simulation results show that the new control strategy reduces NOx emissions at the entrance of the selective catalytic reduction (SCR) system by about 20% at medium–low loads, compared to those based ...

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.