Abstract
In the paper new algorithms for detection of internal inter-turn faults in power transformers are described. Such faults are extremely difficult to detect since they induce negligible increase of the currents at the transformer terminals, although the currents flowing at the fault place are very high and dangerous for the transformer to be protected. The algorithms developed are based on the differential equation of the equivalent circuit of the transformer. In one version additional information from a CT installed inside of the triangle of delta side windings is used, which brings very promising results. Theoretical investigations are supported and illustrated with simulation studies performed both with MATLAB and EMTP-ATP programs.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.