Abstract

In long line applications that involve tripping the faulted phase in case of LG faults, single-pole autoreclosure is extensively used. Traditional phase selectors can suffer some deficiencies in their performance due to varying system and fault conditions. However, the advent of wavelet transform techniques with their ability to focus on system transients provides an effective and reliable method for accurate and fast phase selection. This work describes the design and implementation of a new technique using wavelet transform algorithms. The technique is based on using sharp transitions generated on the faulted phase. This paper presents the wavelet transform concept and its value in classification techniques and feature detection schemes. The feature extraction principle is derived. Generated data from the simulation of the 400 kV power system using EMTP were used to test the performance of the technique.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.