Abstract
Lightning strokes are a main source of transformer failures in distribution systems. The discharge of a lightning current through a distribution transformer's high-voltage (HV) side arresters leads to a ground potential rise of the transformer tank. In the case of a wye-wye connected transformer with ungrounded HV neutral point, the ground potential rise can drive a current through the low-voltage (LV) side windings that leads to an excessive voltage in the HV side neutral point by inductive transformation. Simulations by a measurement-based model demonstrate that a voltage several times the lightning impulse test voltage can arise in the neutral point, in the case of a close lightning strike to the HV side overhead line. The use of transformer LV side surge arresters in combination with proper grounding on the HV-side are effective ways of reducing the neutral point overvoltage.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.