Abstract

Abstract In every urban infrastructure, Wastewater Treatment Plant (WWTP) requires special attention because of its adverse effects on the environment and also for resource recovery. Therefore, there arises a need to treat the wastewater in order to meet the effluent norms prior to discharge. Different control strategies and various scenarios of plant layout can be tested and evaluated through modelling and simulation studies on the benchmark layouts. In this paper, a feedforward nested loop control structure based on ammonia concentration is implemented on Benchmark Simulation Model (BSM1-P) developed based on Activated Sludge Model No. 3 bioP (ASM3bioP) for controlling the dissolved oxygen in aerobic zones and nitrate level in anoxic zones and nutrient removal by adding two anaerobic zones. By using this control strategy, pumping energy, percentage violations of ammonia and nitrogen concentrations in the effluent, and effluent quality are reduced effectively.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call