Abstract

The cascaded H-bridge (CHB) low-capacitance static compensator (LC-StatCom) has a limited negative-sequence current injection capability compared to a conventional CHB StatCom, due to the comparatively larger oscillations on the capacitor voltages. Placing limits on the ability to provide negative-sequence current to the grid for a given capacitor size is required to prevent overmodulation. This article shows that these limits can be maximized by injecting an optimal third-harmonic circulating current. The effects of injecting the third-harmonic current on the capacitor voltages, both in balanced and unbalanced grid voltage conditions, are analyzed. Specifically, the procedure allows the knowledge of the potential capability of the LC-StatCom when injecting negative-sequence currents. The procedure is based on a linear programming approach. Although the procedure is applicable to any CHB StatCom, regardless of the submodule capacitor size, it is particularly important in LC-StatComs. To corroborate the proposed analysis, simulation and experimental results under balanced and unbalanced grid voltage conditions are presented.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.