Abstract
During the fault of the wind power collection line of the MMC-HVDC system, the amplitude of the fault current may be limited due to the control of the converter, which leads to the severe limitation of traditional protection. In this paper, based on the difference of negative sequence current accumulation, a new protection scheme for wind farm collection lines is proposed. First, the negative sequence current equivalent circuit of the wind farm collection line is constructed. Then, the distribution characteristics of negative sequence current at different fault locations are identified. On this base, a novel protection scheme based on transient negative sequence current accumulation difference using interconnected blocking signals is proposed. The RTDS simulation results show that the protection scheme can accurately identify faults of different types and locations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.