Abstract

Loading tests were conducted using column-beam joint specimens with such a shear-bending capacity ratio in the panel zone as specified for practical design. 1) The Q-R curve indicated stable and ductile hysteresis with no rapid strength reduction beyond the maximum strength. 2) No difference was found in Q-R curve envelope between PCa and RC specimens. 3) The maximum strength at the column-beam joint where flexural yielding of the beam preceded could be accurately evaluated by ACI equation for beams. 4) No difference was found between PCa and RC specimens in the relation between equivalent viscous damping factor and inter-story displacement.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.