Abstract

This paper proposes a new current balancer in single-phase three-wire secondary distribution systems using the correlation coefficients. The components of the load currents correlative to the primary side voltage waveform, which correspond to the active currents, are detected in each feeder, then the nonactive and unbalanced-active components are compensated on the source side. The balanced currents with unity power factor are obtained in each feeder. The basic principle of the proposed method is discussed in detail, and then confirmed by digital computer simulation. A prototype experimental system is constructed and tested. Experimental results demonstrate that the balanced source currents with unity power factor are obtained in spite of unbalanced load currents. © 2009 Wiley Periodicals, Inc. Electr Eng Jpn, 169(1): 50–58, 2009; Published online in Wiley InterScience (www.interscience.wiley.com). DOI 10.1002/eej.20843

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.