Abstract

In order to evaluate the corrosion of copper which is used as an absorber vessel material in the absorption refrigeration cycle, electrochemical measurements of copper in the condition of a thin-solution layer, which is 1mm in thickness, of concentrated aqueous solution of lithium bromide in argon atmosphere were made.As a result, values of corrosion rate in the condition of a thin-solution layer were 3 to 6 times larger than in the immersed condition regardless of whether there was an inhibitor or not. This difference seems to be due to the following reason. As the argon gas phase above the solution contained a little air (oxygen), the oxygen concentration was higher in the condition of a thin-solution layer than in the immersed condition. Therefore, the values of free corrosion potential in the condition of a thin-solution layer became more noble than in the immersed condition, and cathodic diffusion limit current density in the condition of a thin-solution layer increased, compared with that in the immersed condition.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.