Abstract

In winter, the content (%) of “multi-conductor simultaneous faults” among “all the lightning faults” on double circuit transmission lines is much larger than in summer. To find a cause of the problem, many field investigations were conducted and statistics were collected. Based on these data, the author set up a new theory to estimate the probability of occurrence of multi-conductor faults during winter. This results coincide with the lightning performance of transmission lines either in summer or winter. The author's important view points which are newly introduced are followings; (1) The content (%) of large current lightnings among all the lightnings is much larger in winter than in summer (2) More than 83% of lightning flashes hit tower tops in winter, while only 25% hit tower tops in summer.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.