Abstract

It is well known that the phase distribution of partial discharge in GIS depends on the source of discharge. However, the equivalent circuit model has not been considered sufficiently. On the other hand, the authors have proposed an extended Whitehead circuit model, and have explained the difference of the phase distribution of discharge. In this paper the case of needle on spacer is treated in a model GIS (300kV), and the difference of phase distribution is measured. Next the dust figures are obtained, and charged regions on the spacer are discussed. Finally, it is stated that the EMTP simulation by the extended Whitehead circuit model agrees with the result of experiments fairly well.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.