Abstract
The main objective of this study was to examine the effectiveness of energy-saving renovation techniques through passive cooling for urban houses in hot-humid climate of Malaysia. Effects of two strategies, i.e. complete natural ventilation (NV) strategy and partial air conditioning (AC) strategy, were simulated using TRNSYS. The results revealed that indoor thermal comfort was achieved in the complete NV strategy by applying multiple passive cooling techniques that prevented external heat on the outer building envelope and night ventilation, even under heated urban climatic conditions. In the partial AC strategy, reductions of about 45% in the sensible cooling load and about 30% in the latent cooling load compared to the current condition were obtained by insulating inner surfaces of the master bedroom while applying several passive cooling techniques to the other spaces.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of Environmental Engineering (Transactions of AIJ)
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.