Abstract

It has been reported that the calculated values of field transient behavior in a synchronous machine differ considerably from the measured values. This discrepancy is caused by the use of equivalent circuit constants in standardized tests provied by JEC2130 and IEC60034-4, in which the mutual leakage reactance between the damper and field windings is not accounted for. The authors have been studying a method for calculating equivalent circuit constants for the accurate simulation of transient behavior including the field winding side, by means of a standstill test with a small-capacity DC power supply (DC decay testing method). The authors have previously presented a calculation method using operational impedances with the field windings opened, shorted, and inserted with an external resistance, obtained by the DC decay test. This paper presents a new method in which the external resistance used in our previous method is no longer needed. Instead, the field winding impedance is determined based on its invariability against slip. The validity of the new method is demonstrated by comparing the calculated and measured values of the armature and field currents during a sudden three-phase short-circuit using 10kVA-200V-31.9A-4P-50Hz test machines.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call