Abstract

This paper proposes a PWM (pulse-width-modulation) control of a pneumatic single-rod cylinder positioning system. In the system, the rod chamber pressure of the cylinder remains constant, and the head chamber pressure is controlled by two solenoid valves. The valves are under PWM mode control. In synthesizing the PWM servomechanism, the solenoid valves are characterized by a static characteristic equation incorporating the nonlinear elements caused by the switching time of the valve. The proposed PWM method can assign the steady-state duty ratios of the valves to the desired locations of their flow characteristics, which makes it possible for the system to avoid the dead-zone or the nonlinear region caused by the PWM solenoid valves. Also, a threshold near the desired position is set up so that the valves are closed at steady state. An experimental study of the proposed system is performed. These experiments verify the theoretical design work, and indicate that the proposed control system is feasible for pneumatic positioning.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.