For the demonstration of feasibility and loss-reduction effect of the larger-capacity amorphous core transformers (AMT), this paper proposed the support structure and design method of the iron-loss reduced amorphous wound cores with a weight of 7 tons. We designed and manufactured 10 MVA single-phase test model with the cores inserted in a support cage having structures of the stress-buffered core support, the proof electromagnetic force from the windings, and the stray loss-reducing shields. The 50%-loaded total loss of the test model estimated from the calculated and measured results has been reduced by 35% compared with a conventional silicon-steel core transformer (SST) with the same power capacity.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.