Abstract

開放型蓄熱水系の空調用熱源機銅管に対する酸素低減処理の腐食抑制効果を明らかにするため,熱源機銅管の渦流探傷調査報告書の解析と熱源機運転期間中の冷水や温水の溶存酸素(DO)濃度の解析を行った.銅管肉厚の5%以上が減肉した場合を損傷銅管とし,渦流探傷調査を行った銅管数に対する損傷銅管数の割合を損傷率とした.その結果,DO濃度の減少に伴い銅管の損傷率は低減し,DO濃度1mg/L以下にすれば損傷率を1%以下にできることがわかった.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.