Abstract
In this study, experiments were conducted to develop a means to estimate mass flow rate of opening jet plume. From the results obtained through small and middle-scale experiments, the following findings were obtained: (1)when the opening jet plume is modeled into a vertical plume, the height Z_D at which the mass flow rate becomes equal to the opening flow rate depends only on the section height of opening jet in any geometry of the opening, (2)The nondimensional height of virtual origin of opening jet plume depends only on the nondimensional mass flow rate of opening jet, (3)The mass flow rate of the small and middle-scale experiments are well scaled by nondimensional mass flow rate of opening jet and nondimensional entrainment length. And (4)when using opening width for the representative length, the nondimensional mass flow rate μ_p is given by μ_p=0.19{(Z_e+ Z_D+Z_0/B}^<5/3> regardless of the opening shape and temperature of opening jets.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of Architecture and Planning (Transactions of AIJ)
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.