Abstract

Lightning faults on transmission lines often cause instantaneous voltage drops in power systems. Influences of instantaneous voltage drops become increasingly serious in high technology industries etc. As countermeasures of instantaneous voltage drops, uninterruptible power supplies (UPS) are employed. On the other hand, line surge arresters are installed on transmission lines increasingly as one of the effective countermeasures of double-circuit faults caused by lightning strokes. Additionally, the arresters are effective as one of the reduction methods for the frequency of instantaneous voltage drops. In this paper, the frequency of instantaneous voltage drops reduced by installation of line surge arresters on transmission lines is estimated by employing EMTP analysis. Also, the accuracy of the method in estimating the frequency of instantaneous voltage drops in power systems is evaluated through comparison with experience.