Abstract

The net thermal radiation of hot water panel was measured in accordance with the new measurement method using the radiant illumination meter, developed by Heating Machinery Society of Japan in 1987. The main results are shown as follows : (1) The ratio of radiation to total output of single panel and double panel are 20〜30% and 11〜14%, respectively, regardless of temperature difference between room air and hot water in panel. (2) the measured values are 0〜20% greater than predicted values of thermal radiation based on Hottel's radiant theorem.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.