Abstract
The mutual inductances between crossing three-phase power lines and communication lines, both with earth return, are studied. Infinitely and finitely long power lines are both considered, and the terminal effect from the earth is taken into account. By applying the complex image theory and superposition principle, analytical solutions to the mutual inductances are derived. The solutions are valid for both oblique and parallel proximity. Comparison made with experimental results shows that the derived formulas are sufficiently accurate. In practical applications, the measured value of the earth conductivity should be used in order to obtain a higher accuracy. >
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.