Abstract

This paper presents a new method for modeling the steady-state behavior of the currents transmitted between the windings of a transformer subjected to an inter-turn short-circuit fault (ITSC). ITSC is one of the most frequent and most damaging faults in magnetically coupled circuits, which occur in power transformers. Coupled Electromagnetic Circuit (CEMC) Model modeling the reasoning and relationships describing the operating principle of a power transformer through the electrical and magnetic parameters defined by the self and mutual inductances that influence the voltages and currents transmitted between the transformer windings. The representation of the state variable equations of a proposed model of a three-phase multi-turn transformer in healthy mode (no fault) and in degraded mode (with inter-turn short-circuit faults of 10%, 20% and 30%) has been implemented using a program inserted in MATLAB software. The simulations illustrate the evaluation of the primary and secondary currents as well as the voltage drop across a load, and the accuracy of the state model based on the coupled circuits was validated. The results obtained can provide a basis for the design of the short circuit of the multi-turn transformer.