Abstract

The presence of moisture in a power transformer is harmful to its oil–cellulose system and can also accelerate the ageing. Therefore, it is necessary to estimate the moisture content inside the transformer. Due to the variation of loading conditions and ambient temperatures, moisture is neither in a static state nor uniformly distributed in transformers. Moisture migrates between oil and cellulose and moves inside oil and cellulose of transformers. Moreover, given the complexity of a transformer's structure, moisture distribution is also a function of mass and dimensions of transformer's oil–cellulose system. This study adopts a multi-physics modelling approach to investigate moisture dynamics in transformers. In this approach, moisture dynamics is investigated by coupling electromagnetic, thermal, fluid flow and moisture migration physics simultaneously. An accurate estimation on moisture distribution in transformers can then be obtained. Extensive ageing and moisture diffusion experiments have been conducted on a prototype transformer to verify the proposed approach.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.