The Stirling cooler is a potential substitute for the vapor compression refrigeration system in a moderate-temperature zone. An isothermal model of a Stirling cooler based on finite time thermodynamics is established. The expressions of input power, cooling capacity, and coefficient of performance (COP) are derived. The input power, cooling capacity, and COP of the Stirling cooler are optimized simultaneously using the particle swarm optimization (PSO) algorithm. The performance of the multi-objective particle swarm optimization (MOPSO) algorithm is tested by four benchmark functions. The technique for order preference by similarity to an ideal solution (TOPSIS) is used to obtain the global optimal solution. According to the global optimal solution, the Stirling cooler obtains the performance with an input power of 106.5 W, a cooling capacity of 266.7 W, and a COP of 2.5. Compared with the results obtained by the single-objective optimization of cooling capacity, the COP increases by 42.0%, and the input power decreases by 59.3%. Finally, a sensitivity analysis of heat exchangers on the cooling capacity is carried out. The result shows that the cooling capacity is more sensitive to the hot-side heat exchanger in the optimal design point.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.