Abstract

The main objective of the present study is to perform the thermodynamic, economic and environmental analyses of a solar-geothermal driven combined cooling, heating and power (CCHP) cycle integrated with flat plat collectors containing water/copper oxide (CuO) nanofluid as the absorbing medium. Twelve main parameters are selected as the decision variables of the desired system while the daily exergetic efficiency, total product cost rate and total product environmental impact associated with exergy rate are chosen as the three main objective functions. NSGA-II (Non-dominated Sort Genetic Algorithm-II) is individually applied to obtain the final optimal solutions in the multi-objective optimization of the desired system for four working fluids including R134a, R423A, R1234ze and R134yf from the exergy, exergoeconomic and exergoenviromental points of view. Based on the multi-objective optimization outcomes, R1234ze is the best fluid with 36.82Pts/h total product environmental impact rate so that the maximum nanoparticles volume fraction and minimum collector tilt angle are required. Moreover, R423A with the minimum total product cost rate of 4496 $/year is the best fluid at which minimum collector area is needed. Furthermore, R134a is the best fluid with 4.194% daily exergetic efficiency so that the minimum nanoparticle volume fraction is required compared with other studied fluids.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call