Abstract
This paper presents multi-stress chamber experiments and tracking wheel tests to examine the tracking and erosion performance of polymer insulators for transmission. Multi-stress testing is able to demonstrate deficiencies of polymer insulator materials and designs, including the nature of interfaces in insulation design. We have investigated IEC 61109 Annex C (5000 h aging test) and CEA tracking wheel test as test methods of artificial accelerated aging. The aging degree of the polymer insulator is estimated by leakage current, measurement of hydrophobicity degree, damage conditions of the insulator surface, and withstand voltage tests.