In the study of power grid security, the cascading failure analysis in multi-contingency scenarios has been a challenge due to its topological complexity and computational cost. Both network analyses and load ranking methods have their own limitations. In this paper, based on self-organizing map (SOM), we propose an integrated approach combining spatial feature (distance)-based clustering with electrical characteristics (load) to assess the vulnerability and cascading effect of multiple component sets in the power grid. Using the clustering result from SOM, we choose sets of heavy-loaded initial victims to perform attack schemes and evaluate the subsequent cascading effect of their failures, and this SOM-based approach effectively identifies the more vulnerable sets of substations than those from the traditional load ranking and other clustering methods. As a result, this new approach provides an efficient and reliable technique to study the power system failure behavior in cascading effect of critical component failure.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.