Abstract
This article describes measurements of the surge voltage characteristics from a group of eight low-voltage motors driven by inverter fed drives. As described here, two motors have repeatedly been subjected to unexpected stator winding failures. Inspection of the windings after failure indicated that the main cause of the failures is the voltage surge environment applied to the stator winding.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have