Abstract

Failure investigation of four 21,000 HP synchronous motors concluded that the cause is related to voltage surges and as a result surge protection was applied to all 13.2 kV motors in the plant. (Ref.l) Further failures of three 21,000 HP synchronous motors after the installation of surge arresters indicated an inadequacy of the specified surge protection. Two of the failed motors were tested at the manufacturer's facility to investigate the cause of failure. Test results concluded that insulation failure was caused by the combined effects of prior insulation degradation and inadequate surge protection. This paper presents an investigation into the three failed motors.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.