Abstract
Inadvertent failure of a HV gas-insulated system (GIS) is traced to a seemingly innocuous mechanism in particle-induced breakdown. Impending dangers from inconspicuous conducting particles in a large physical system are quite intriguing. The dynamic behavior of the particle due to electric field/particle/fluid medium interaction is a complex phenomenon. To understand this interaction a credible database has been generated for the field-induced motion of the particles on a physical prototype model. Induced surface charge acquired by the particle is calculated based on the proposed model (field calculations) and by considering it to be a prolate ellipsoid. Methods for deactivating potentially dynamic particles using dielectric coated active parts and grounded enclosures, and a novel technique called reverse polarity charging have been suggested. Performance of GIS in the presence of metallic particles has been studied with bare electrodes and with dielectric coatings of different conductivities with a view to obtain an optimal value of the conductivity.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Dielectrics and Electrical Insulation
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.