Abstract

Cooling towers have the potential to develop infectious concentrations of Legionella pneumophila. Legionella counts increases where biofilm and warm water temperatures are present. In this study, biofilm associated L. pneumophila and heterotrophic bacteria were compared in terms of material dependence. Model cooling tower system was experimentally infected by L. pneumophila standard strain and monthly monitored. Different materials were tested for a period of 180 days. The lowest L. pneumophila and heterotrophic plate counts were measured on plastic polymers, whereas L. pneumophila and heterotrophic bacteria were accumulated rapidly on galvanized steel surfaces. It can be concluded that selection of plastic polymers, as a manufacturing material, are suitable for recirculating water systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.